GENERAL
UPS Type | Tower |
Phase | Single phase with ground |
Rating (VA) | 10000 |
Nominal Power (W) | 8000 |
Standard Model Dimension (mm) | 442 x 190 x 688 (D x W x H) |
Weight (kg) | 66 |
Long-run Model Dimestions (mm) | 442 x 190 x 318 (D x W x H) |
Weight (kg) | 16 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 208/220/230/240VAC |
Voltage Range | 110-300 VAC (Load at 50%) 176-300 VAC (Load at 100%) |
Frequency Range | 46~54 Hz or 56~64 Hz |
Power Factor | >= 0.99 |
OUTPUT
Connection Type | Terminal |
Output Voltage | 208/220/230/240VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range)Â | 46~54 Hz or 56~64 Hz |
Frequency Range (Batt. Mode) | 50Hz or 60Hz +/-0.1Hz |
Current Crest Ratio | 3:1 |
Harmonic Distortion | ≤3% THD (Linear load) ≤5% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
LCD | Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232* USB Port Emergency Power Off (EPO) |
BATTERY
Standard Model Type | 12V / 9Ah |
Numbers | 16 |
Typical Recharge Time | 9 hours recover to 90% capacity |
Long-run Model Type | Depending on the capacity of external batteries |
Number | 16 ~ 20 (Adjustable) |
Charging Current (max) | 1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries) |
REAR PANEL
|